TECHNICAL SPECIFICATIONS
|
||||||||
|
MODEL
|
|
SDU 3300
|
SDU 4000
|
SDU 5000
|
SDU 6000
|
SDU 8000
|
SDU 10000
|
|
|
Power
|
:
|
3300VA/
2300W
|
4000VA/
2400W
|
5000VA/
3500W
|
6000VA/
4200W
|
8000VA/
7200W
|
10.000VA/
9000W
|
|
|
Technology
|
:
|
On-line double conversion - Online double conversion
|
||||||
|
INPUT (INPUT)
|
||||||||
|
Rated voltage
|
:
|
1 pha 220-230-240 Vac
|
||||||
|
Minimum voltage
|
:
|
164 VAC at 100% load / 84 VAC at 50% load
|
||||||
|
Power factor
|
:
|
>0.98
|
||||||
|
Rated frequency
|
:
|
50/60 Hz ± 5 Hz
|
||||||
|
BYPASS
|
||||||||
|
Voltage
|
:
|
180-264 VAC (Economy Mode or Smart Active Mode selectable)
|
||||||
|
Frequency
|
:
|
50/60 Hz ± 5 Hz
|
||||||
|
OUTPUT (OUTPUT)
|
||||||||
|
Voltage
|
:
|
1 pha 220-230-240 Vac
|
||||||
|
Voltage distortion
|
:
|
<3% with linear load / <6% with non-linear load
|
||||||
|
Frequency
|
:
|
50/60 Hz ± 5 Hz
|
||||||
|
Waveform
|
:
|
Sinewave
|
||||||
|
BATTERY
|
||||||||
|
Battery Type
|
:
|
VRLA AGM, sealed, maintenance-free
|
||||||
|
Charging time
|
:
|
4-6 hours
|
||||||
|
OVERLOAD TIME
|
||||||||
|
100%<Load<110%
|
:
|
1 minute
|
||||||
|
110%<Load<150%
|
:
|
4 seconds
|
||||||
|
Load>150%
|
:
|
0.5 seconds
|
||||||
|
OTHER INFORMATION
|
||||||||
|
Communication port
|
:
|
RS232, USB, communication slot, Powershield3 software allows UPS control and monitoring
|
||||||
|
Power input socket
|
:
|
1 IEC 320 C20
|
Terminal board
|
|||||
|
Power output socket
|
:
|
2 IEC 320 C13 + 1IEC 320 C20
|
Terminal board + 2 IEC 320 C13
|
|||||
|
Minimum backup time
|
:
|
12 min
|
10^ min
|
10^ min
|
8* min
|
8* min
|
6* min
|
|
|
Dimensions
(WxDxH) |
:
|
175 x 520 x 455 : Tower
19” x 520 x 4U : Rack |
175 x 660 x 455: tower
19” x 660 x 4U : Rack |
2 x (175 x 660 x 455): Tower
2 x (19” x 660 x 4U): Rack |
||||
|
Weight (Kg)
|
:
|
38 (kg)
|
40 Kg
|
62 Kg
|
64 Kg
|
94 Kg
|
95 Kg
|
|
|
Main function
|
:
|
Suitable for: server rooms, network equipment, ATMs, telecommunications equipment, security, analysis, measurement, medical testing equipment, printing-prepress equipment, specialized electronic equipment and many other important fields
|
||||||
|
Warranty
|
:
|
2 years including the battery
|
||||||
Product Categories
- Product
- High-end Karaoke & Entertainment Solutions for home and business
Sentinel DUAL (High Power) is a Riello SDU5000 UPS
Short Description
Key features :
• UPS can be installed vertically (tower) or horizontally (rackmount), depending on customer preference.
The front of the digital display can be pulled out (using the provided keys) and rotated to suit the installation format.
• Low noise level (< 40dBA) thanks to PWM digital ventilation systems that control load- and temperature-dependent fan speed, using an inverter with a switching frequency (> 20kHz, above the audible range). Dual DIALOG is suitable for installation in any environment.
User option :
• Operating mode:
- On-line (VFI): runs continuously
- The UPS supports the load from the battery supply when the mains power fails or experiences sudden fluctuations.
- Smart UPS automatically operates in on-line mode (VFI) or line-interactive mode (VI); the mode depends on the stability of the power supply
- Emergency: The UPS only supports the load with its battery when there is no power - suitable for emergency lighting
- Conversion frequency of 50 or 60Hz
• Output voltage selection: 220-230-240 VAC single-phase or 380-400-415 VAC three-phase
• Automatic power restart via PowerShield³ software
• Ends battery discharge before the alarm.
POWER QUALITY
• Filtering, stable and reliable voltage - Online double-conversion (VFI) technology compliant with EN50091-3, with EMI filters
• Ensures typical output quality with IT load distortion at crest factors of 3:1
• Low impact on the power source, like a UPS with a sine wave input available today.
VERY RELIABLE
• Fully digital control
• No interruption via automatic bypass
• Bypasses can be activated manually
• Uses IMS (Insulated Metal Substrate) modules.
ADVANCED DIAGNOSTICS
• Status, measurements, and alarms available on the standard backlit display
• UPS can be digitally updated (upgradeable flash) .
• Reliable battery performance (automatic and manual battery testing)
• Extends battery life due to Low Ripple Current Discharge (LRCD)
• User-replaceable
•Backup time can be extended with additional battery packs
ENHANCE VOLTAGE
• Input protected by a resettable thermal-activated breaker
• Back protection: to prevent energy from being fed back into the power source when a fault occurs
• Increased short-circuit current on bypass
• Overload capacity: 150% on the inverter.
• Performance guaranteed at temperatures up to 40°C
• Instructions for switching to bypass.
2-year warranty