UPS 3 Phase 300kVA Delta Turkey – DSD3300

Contact

Short Description

Products are manufactured and imported synchronously from Europe – 12-month warranty – spare parts support for up to 10 years.

  • Support – Project protection
  • Providing complete import documentation
  • Technical team trained methodically, holding professional certificates issued by the manufacturer
  • Product maintained every 6 months
  • Free site survey and solution consultation support
  • Specifications
    1. MODELdlt:

       DLT 3100 DLT 3120 DLT 3160 DLT 3200 DLT 3250 DLT 3300

      Power

       100 kVA  120 kVA 160 kVA 200 kVA 250 kVA 300 kVA

      INPUT Voltage220 / 400 Vac 3 Phase +N, +/-% 15By-Pass Voltage220 / 400 Vac 3 Phase +N, +/-% 10Input Frequency50 Hz, +/- %5EMIEN50091 -2 Class AInput out of Tolerant ProtectionElectronic input out of tolerant protectionOUTPUT Power (kW)

      80 96 128 160 200 240

      Power Factor0,8Voltage220/400 Vac 3 Phase+NFrequency50 Hz. (60Hz On Request)Frequency Tolerance+1-2% (Line Synchronized) • +/-0,2% (Free Running)Efficieny at 100% Load%90-92Crest Factor3:1Overload Protection

      100 % 125% Load : 10 min • 125 % 150% Load : 1 min  • <150% Load : By-Pass

      Short Circuit ProtectionElectrolnc short circuit protectionTfahage out of ldemt ProtectionElectronic out of tolerant protectionTotal Harmonic Distortion<3%THDNon Linear Load <%5BATTERIES Battery TypeSealed Lead Acid – Maintenance FreeNumber of Batteries

      30 32

      Float Charging Voltage

      405 VDC 432 VDC

      End of Discharge Voltage

      300 VDC 320 VDC

      Ambient Temperature c25 c°Battery Voltage ProtectionElectronic Battery out of tolerant protectionBattery ProtectionAutomatic circuit breakerBattery TestAutomatic every 72 hoursGENERAL CommunicationRS232 + Dry ContactsTemperature Range0C° – 40 c°Humidity (Non Condensed)90 % (Non condensed)Protection DegreeIP20Altitude< 1000 m. above sea levelNoise level< 65 dBA < 70 dBAWeight without batteries (kg)750 765 810 970 1330 1370Dimensions (mm) HxWxD1650x1100x800 1730x1195x870 1880x1565x925VentilationForced air cooling.OPTIONS

        ACCESSORIES  

      Input Transformers

        Galvanic Isolation transformer at the Input (In the external cabinet) Monitoring and Control Software  T-MON 3 client standart

      Input THD

       <10%(with 18 Pulse Rectifier .according to UPS range  Multiserver Shutdown Unit  Available as option
        5% (with 18 Pulse rectifier, + filter) upto 80 kVA SNMP CommunknlianAdaptor  Available as option

      Parallel Operation

       1+3 Systems (N+1 redundant, reduntant, symetrlc parallel) Serial Port Enhancer  Available as option

      MBS

       Maiitenanoe by-pass switch for complete isolation (For2062Ơ7&210) MorDusCommutioriion Adaptor  Available as option (over RS485 or over TCP/IP)

      300kVA 3/3 UPS – Integrated output isolation transformer – suitable for industrial loads, motor loads…