| MODEL |
|
| DLT 3100 |
DLT 3120 |
DLT 3160 |
DLT 3200 |
DLT 3250 |
DLT 3300 |
|
| Power |
| 100 kVA |
120 kVA |
160 kVA |
200 kVA |
250 kVA |
300 kVA |
|
| INPUT |
|
| Voltage |
220 / 400 Vac 3 Phase +N, +/-% 15 |
| By-Pass Voltage |
220 / 400 Vac 3 Phase +N, +/-% 10 |
| Input Frequency |
50 Hz, +/- %5 |
| EMI |
EN50091 -2 Class A |
| Input out of Tolerant Protection |
Electronic input out of tolerant protection |
| OUTPUT |
|
| Power (kW) |
|
| Power Factor |
0,8 |
| Voltage |
220/400 Vac 3 Phase+N |
| Frequency |
50 Hz. (60Hz On Request) |
| Frequency Tolerance |
+1-2% (Line Synchronized) • +/-0,2% (Free Running) |
| Efficieny at 100% Load |
%90-92 |
| Crest Factor |
3:1 |
| Overload Protection |
| 100 % 125% Load : 10 min |
• 125 % 150% Load : 1 min |
• <150% Load : By-Pass |
|
| Short Circuit Protection |
Electrolnc short circuit protection |
| Tfahage out of ldemt Protection |
Electronic out of tolerant protection |
| Total Harmonic Distortion |
<3% |
| THD |
Non Linear Load <%5 |
| BATTERIES |
|
| Battery Type |
Sealed Lead Acid – Maintenance Free |
| Number of Batteries |
|
| Float Charging Voltage |
|
| End of Discharge Voltage |
|
| Ambient Temperature c |
25 c° |
| Battery Voltage Protection |
Electronic Battery out of tolerant protection |
| Battery Protection |
Automatic circuit breaker |
| Battery Test |
Automatic every 72 hours |
| GENERAL |
|
| Communication |
RS232 + Dry Contacts |
| Temperature Range |
0C° – 40 c° |
| Humidity (Non Condensed) |
90 % (Non condensed) |
| Protection Degree |
IP20 |
| Altitude |
< 1000 m. above sea level |
| Noise level |
< 65 dBA < 70 dBA |
| Weight without batteries (kg) |
750 765 810 970 1330 1370 |
| Dimensions (mm) HxWxD |
1650x1100x800 1730x1195x870 1880x1565x925 |
| Ventilation |
Forced air cooling. |
| OPTIONS |
|
| Input Transformers |
| Galvanic Isolation transformer at the Input (In the external cabinet) |
Monitoring and Control Software |
T-MON 3 client standart |
|
| Input THD |
| <10%(with 18 Pulse Rectifier .according to UPS range |
Multiserver Shutdown Unit |
Available as option |
|
| 5% (with 18 Pulse rectifier, + filter) upto 80 kVA |
SNMP CommunknlianAdaptor |
Available as option |
|
| Parallel Operation |
| 1+3 Systems (N+1 redundant, reduntant, symetrlc parallel) |
Serial Port Enhancer |
Available as option |
|
| MBS |
| Maiitenanoe by-pass switch for complete isolation (For2062Ơ7&210) |
MorDusCommutioriion Adaptor |
Available as option (over RS485 or over TCP/IP) |
|